GLN-BT 51.2V 200Ah LiFePO4 10.24KWh Deep Cycle Super Battery Life
GLN-BT 51.2V 200Ah LiFePO4 10.24KWh Deep Cycle Super Battery Life
Overview:
NO | Projects | Specification | Remark |
Cell unit parameter | |||
1 | Battery types and materials | LiFePO4 |
|
2 | Rated voltage/capacity | 3.2V/200Ah |
|
3 | Single battery voltage range | 2.5V~3.65V |
|
4 | Single battery weight | 4.0Kg |
|
5 | The battery's internal resistance | ≤ 0.4mΩ |
|
6 | Module size | 174*54*201mm(L*W*H) |
|
Battery parameter | |||
1 | Rated voltage | 51.2V |
|
2 | Rated capacity | 200Ah |
|
3 | Battery pack voltage range | 43.2V~58.4V |
|
4 | (kWh) Total Power | 10.24kWh |
|
5 | Combination | 1P16S |
|
6 | (Ω)Insulation resistance test value | ≥20MΩ |
|
7 | Operating temperature | Charging 0 ~ 50℃; Discharging -20 ~ 55℃ |
|
8 | Standard charging current | ≤100A | Parallel version with 20A (charging current limit) |
9 | Standard discharge current | ≤100A |
|
10 | Gross weight | 88Kg |
|
11 | Battery Modle size | L510*W250*H520±2mm |
|
12 | Installation Method | Floor |
|
13 | communication | RS485/RS232 | Optional |
Product Electric Performance Test:
No. | Items | Test Conditions | Requirements |
1 | Open circuit voltage | Open circuit voltage measured within 24 hours after standard charge | ≥51.2V |
2 | Impedance | Under the condition of full power, the AC impedance of AC1kHz is measured | ≤20mΩ
|
3 | Capacity retention | Fully charging, store them at (20±5)℃ for 28 days, then discharge to 40.0V @0.2C. | ≥300min Discharging time≥300min |
4 | Cycle Life @25℃ | Discharge to 40.0V @0.2C, then Charge the battery @0.2C to reach 58.4V. Then charge the battery at constant 58.4V voltage until the charging current decreasing to 0.02C. Rest for 10 min. discharge to 40.0V@ 0.2C and rest for 10 min. Continue the charge/discharge cycles until discharge capacity lower than 80% of rated capacity. | Cycles life ≥2000 |
5 | storage | Charge the battery to 40%~65% of its rated capacity using standard charging mode, then keep it in an 20℃±5℃, humidity 45%~85% room for 12 months, fully charge and discharge it @0.2C until voltage down . (The testing sample should be within 3 months dated from production date) | ≥300min Discharge time≥300min |
Please read the specification carefully before install: GLN-ED-067