The second generation of Growatt SPF 5000TL HVM-WPV-P
Size:ES-5KW 48V inverter
This is a multifunctional off-grid solar inverter, integrated with an MPPT solar charge controller,
a high-frequency pure sine wave inverter, and a UPS function module in one machine,
which is perfect for off-grid backup power and self-consumption applications. This inverter can work with or without batteries.
Features
Specifications | ||
Table 1 Line Mode Specifications | ||
INVERTER MODEL | SPF 3500 ES | SPF 5000 ES |
Input Voltage Waveform | Sinusoidal (utility or generator) | |
Nominal Input Voltage | 230Vac | |
Low Loss Voltage | 170Vac±7V (UPS); 90Vac±7V (Appliances) | |
Low Loss Return Voltage | 180Vac±7V (UPS); 100Vac±7V (Appliances) | |
High Loss Voltage | 280Vac±7V | |
High Loss Return Voltage | 270Vac±7V | |
Max AC Input Voltage | 300Vac | |
Nominal Input Frequency | 50Hz / 60Hz (Auto-detection) | |
Low Loss Frequency | 40±1Hz | |
Low Loss Return Frequency | 42±1Hz | |
High Loss Frequency | 65±1Hz | |
High Loss Return Frequency | 63±1Hz | |
Output Short Circuit Protection | Circuit Breaker | |
Efficiency (Line Mode) | >95% ( Rated R load, battery full charged ) | |
Transfer Time | 10ms typical, 20ms Max@ Single <30ms @ Parallel | |
Table 2 Inverter Mode Specifications | ||
INVERTER MODEL | SPF 3500 ES | SPF 5000 ES |
Rated Output Power | 3.5KVA/3.5KW | 5KVA/5KW |
Output Voltage Waveform | Pure Sine Wave | |
Output Voltage Regulation | 230Vac±5% | |
Output Frequency | 50Hz | |
Peak Efficiency | 93>% | |
Overload Protection | 5s@≥150% load; 10s@110%~150% load | |
Surge Capacity | 2* rated power for 5 seconds | |
Nominal DC Input Voltage | 48Vdc | |
Cold Start Voltage(Lead-Acid Mode) | 46.0Vdc | |
Cold Start SOC(Li Mode) | Default 30%, Low DC Cut-off SOC +10% | |
Low DC Warning Voltage (Lead-Acid Mode) | 44.0Vdc @ load < 20% | |
42.8Vdc @ 20% ≤ load < 50% | ||
40.4Vdc @ load ≥ 50% | ||
Low DC Warning Return Voltage (Lead-Acid Mode) | 46.0Vdc @ load < 20% | |
44.8Vdc @ 20% ≤ load < 50% | ||
42.4Vdc @ load ≥ 50% | ||
Low DC Cut-off Voltage (Lead-Acid Mode) | 42.0Vdc @ load < 20% | |
40.8Vdc @ 20% ≤ load < 50% | ||
38.4Vdc @ load ≥ 50% | ||
Low DC Cut-off Voltage (Li Mode) | 42.0Vdc | |
Low DC Warning SOC (Li Mode) | Low DC Cut-off SOC +5% | |
Low DC Warning Return SOC (Li Mode) | Low DC Cut-off SOC +10% | |
Low DC Cut-off SOC(Li Mode) | Default 20%, 5%~30% settable | |
High DC Recovery Voltage | 56.4Vdc(C.V. charging voltage) | |
High DC Cut-off Voltage | 60.8Vdc | |
No Load Power Consumption | <60W | |
Table 3 Charge Mode Specifications | ||
Utility Charging Mode | ||
INVERTER MODEL | SPF 3500 ES | SPF 5000 ES |
Charging Algorithm | 3-Step | |
Max. AC Charging Current | 60Amp(@VI/P=230Vac) | 80Amp(@VI/P=230Vac) |
Bulk Charging Voltage Flooded Battery | 58.4Vdc | |
AGM / Gel Battery | 56.4Vdc | |
Floating Charging Voltage | 54Vdc | |
MPPT Solar Charging Mode | ||
Max. PV Array Power | 4500W | 6000W |
Max. PV Input Current | 18A | |
Start-up Voltage | 150Vdc±10Vdc | |
PV Array MPPT Voltage Range | 120Vdc~430Vdc | |
Max. PV Array Open Circuit Voltage | 450Vdc | |
Max. PV Charging Current | 80A | 100A |
Max. Charging Current (AC Charger Plus Solar Charger) | 80A | 100A |
Table 4 General Specifications | ||
INVERTER MODEL | SPF 3500 ES | SPF 5000 ES |
Safety Certification | CE | |
Operating Temperature Range | 0℃ to 55℃ | |
Storage temperature | -15℃~ 60℃ | |
Humidity | 5% to 95% Relative Humidity (Non-condensing) | |
Altitude | <2000m | |
Dimension(D*W*H), mm | 485 x 330 x 135 | |
Net Weight, kg | 11.5 | 12 |
Question: | so this inverter will not work in the USA |
Answer: | Some Household appliances need 220VAC power, This inverter output is 220VAC, if you have such needed, you can purchase this inverter. |
Question: | is this european 220-240 or is this north america split phase 110-220 |
Answer: | YES. This inverter‘s output is 220VAC you can use in Europe. |
Question: | Soporta baterías de GEL? |
Answer: | yes |
Question: | Is it possible to charge my batteries using the 220VAC for the input and use 120v for the output at the same time to power my outlets? |
Answer: | NOT. Inverer is OK to charge my batteries using the input 220VAC. But can't output 120VAC. This is 220V inverter, its output is 220V. |
Question: | will this inverter feed back to the grid |
Answer: | NO. This inverter is Off-grid inverter, it can work with or without battery. IF you need feed back to the grid, you need a Grid Tie Inverter,not this model. |
Question: | Does this unit work with lithium batteries? |
Answer: | yes. |
Question: | Not sure i understood the 220vac answer.i'm in the us, can i have electrician install 220vac outlet next to my dryer 220v and have this inverter work? |
Answer: | About 220vac‘s Explanation, 1. This inverter output is 220V AC. ------If your dryer need 220VAC power, then you can use inverter's output power directly to your dryer or other Electrical appliances which require 220V AC power. 2. If you have 48V battery, Usually you can use solar panels to charge battery and Storing energy, but if your solar panel is not avaliable, then you also can use 220V AC power to charge your battery, Storing energy for daily use.(this inverter can work with or without battery, if you don't have battery, is also ok.) 3. YES. You can use 220V AC power let this inverter work. |
Question: | side label indicates 50/60hz is this configurable in the settings? what is the Inverter weight? |
Answer: | yes. 50/60hz can be set by yourself. Include its package weight 32.18lb(14.6kg), item's Net Weight is 26.45lb(12kg). Dimension(D*W*H), mm: 485 x 330 x 135 |
Question: | do I need to buy separate solar panels? |
Answer: | YES. IF your wanna use solar panel to power your load or charge your battery. |
Question: | Does it shut off when overloaded or does it switch to utility power? |
Answer: | This can be set, it depends on your need. Setting[18:Overload enable bypass] choose enabled; When this setting choose "enabled", if an overload occurs in battery mode, the inverter will switch to utility power your load. |
- Administrator reply
- Hello, our service will contact u soon.